2110 Temperature Controller
Chromalox 2110
7
Good Wiring
Practices
Separate wire into bundles—When planning the system wiring,
separate wiring into functionally similar bundles, e.g.
• Powerleads
• Sensorleads(ifpowerleadsmustcrosssensorleads,theyshould
cross at a 90° angle)
• Outputsignallines
Separate sources of electrical noise—Locate all sources of electrical
noise in your system, and separate these sources from the control
system, e.g.
• Motors
• Contacts
• Solenoids
Electrical noise can affect the function of any control system. When
driving a contactor coil or other inductive load, an appropriate rated
AC snubber circuit is recommended (Chromalox Part No. 0149-01305).
Connect before power is applied—Make all electrical wiring connec-
tions to the back of the controller before power is applied to the unit.
C
omply with regulations—WARNING: All wiring practices must com-
ply with local regulations. Failure to do so could result in damage to
controller and/or personal injury or death from electrical shock.
This instrument is intended for panel mounting and the terminals
must be enclosed within a panel. Use National Electric Code (NEC)
Class 1 wiring for all terminals except the sensor terminals.
Check wiring decal—Check the wiring decal on the side of the unit
to verify the model number. The wiring decal shows the wiring ter-
minations. All wiring will be connected to the terminals on the back
of the instrument case. Specific wiring instructions for different input
and output types are given in this section. See also Figure 3.5.
Additional information—For sensor wiring practices, see “Sensor
Input Wiring”. For additional information on good wiring practice, re-
quest IEEE Standard No. 518-1982 from IEEE, 345 East 47
th
St., New
York, NY 10017 or www.ieee.org.
Section 3–Installation and Wiring
!
Figure 3.5
Wiring Terminal Identification
NC
NO
COM
Sensor Input
Wiring
Output
Wiring
(S1, S2)
Output Wiring
(R1, R3, V0, or S0)
Instrument
Power Wiring
Alarm Wiring